Measurement:Elevation
Appearance
Node Elevation Measurement
1. Context
In field deployments, it may appear convenient to use smartphone GPS readings to determine the elevation of pipe network nodes.
However, GPS-based altitude measurements are often insufficient for infrastructure-grade water systems due to:
- low vertical accuracy in consumer devices
- atmospheric variation
- inconsistent reference datums
- drift over time
As a result, relying solely on GPS elevation can lead to incorrect hydraulic modeling and unsafe system behavior.
2. Normative Requirement
All AOWIS-compliant systems:
- MUST NOT use uncalibrated consumer GPS altitude as the sole source of node elevation data for hydraulic or control decisions
- SHOULD use surveyed or externally validated elevation references where available
- MAY use GPS-derived elevation only as a temporary or fallback estimate, clearly marked as low-confidence
3. Measurement Model
Node elevation values MUST be represented as:
- a numeric value relative to a defined vertical datum
- associated metadata indicating source type
- optional uncertainty or confidence indicator
4. Reference Hierarchy
Preferred sources for node elevation:
1. Geodetic survey measurements 2. Local infrastructure engineering records 3. Differential GPS or RTK systems 4. Consumer GPS (fallback only)
5. Traceability
The restriction on GPS-only elevation sources exists to prevent:
- hydraulic miscalculations
- incorrect pressure modeling
- unsafe valve/pump control decisions